Non-Compliance detail


  
Summary
 
Licence number: 1698
Annual Return Start: 01 May 2010
Annual Return End: 30 Apr 2011
Date Received: 29 Jun 2011
 
Licence Condition numberType of non-complianceEPA actionsNo. of times occurred
L3.1 Point 2 exceeded opacity limit on 173 occasions. Opacity excursions caused by trips of the ESP, gas flow variations & other process disturbances. Operating procedures, training, process alarms & auto operator guidance regularly modified. EPA has written to licensee regarding non-compliance and relevant action 173
M2.1 Point 9 oil & grease not measured daily during discharge. Independent sampling contractor failed to collect samples on 6 occasions. Administrative non-compliance - licensee advised of required action 6